    CONDUCTIVITY METER

 
 

CONDUCTIVITY METER:

The meter is used on sites exposed to rain, dust, and robust handling. Basically, it comes in two parts i.e. Meter & Sensor.

Sensor:
It is the sensing element of meter, which senses the conductivity and sends the signal to the meter.

Meter:
This is the unit that processes the information received from the sensor and displays the actual conductivity in the line.

   
 

Technical Specifications :

SENSOR

MOC

SS316/ABS with ¾” Tee

End Connections

½” / ¾” BSPM

Tee

½” / ¾” equal tee with BSPF threading

Cell Constant

K=0.1(other values optional)

Cable

2 core shielded 3 meter length
(Higher length optional)

Max. operating pressure

5 kg/cm2

METER

Measuring Range

Various Ranges

Parameter sampling rate

2 seconds

Resolution

0.01 to 1 depending on range with auto ranging

Accuracy

± 2% of FSD

Linearity

1%

Supply/Power

230VAC ± 15% / 3 VA

Display

4 Digits LED 7 SEMENT

Enclosure

ABS weather proof

Calibration

Using front keypad

Physical Dimensions

96 x 96 x 150 mm
92 mm x 92 mm (panel cut out)

Temperature

0-60 degree Celsius

Terminals

Sensor screwed type (on pcb)
Mains – 3-core mains chord through gland

Trouble Shooting:

TROUBLE

PROBABLE CAUSE

ACTION

DURING COMMISSIONING

Fluctuating
Reading

Sensor not dipped in the line properly

Loop the outlet tubing such that the tee always remains

Wrong wiring

Connect the wires as per drawing

DURING NORMAL SERVICE

Display
Shows
Erroneous
Reading

Sensor not dipped in the line .properly

Loop the outlet tubing such that the tee always remains flooded with water

Deposition on the sensor

Remove the sensor and clean it with Polish paper

No Display

High Voltage

Check MOV/ FUSE, if it is burnt then replace it with new one

Frequent
Fuse failure

MOV short

Replace MOV*
As well as FUSE**

MOV* - 14 mm Dia. And 320V AC
FUSE** - 500mA

   
 
  Quick Contacts ...

Shop No. 6, Bobby Pathak Avenue, Near Corporation Bank, Opp. Rotary Garden, C.S. Complex, Dahisar (E), Mumbai - 400068, Maharashtra, India
Phone : 91-22-28480866/28482642/28480100/28483848     Fax : 91-22-28480100
Mr. Manu C. Patel (Director) Mobile : +919820684990
Mrs. T. M. Patel (Director) Mobile : +919867397938

Web :- | www.numatikaqua.com | www.indiamart.com/numatikengineers |
           | www.fueladditives.tradeindia.com | www.roplantsanddmplants.com |
           | www.h2obazaar.com/company/numatik |


E-mail :- reponse@roplantsanddmplants.com / manu305@bom8.vsnl.net.in / water.tech60@yahoo.com / numatikengineers@gmail.com

 
| Home | About Us | Product Range | Clients | Downloads | Contact Details | Enquiry Form |